Most adopted state fire codes reference these NFPA standards for the events that trigger a fire watch — confirm the exact citation with your local AHJ.
| Trigger | Threshold | Code |
|---|---|---|
| Fire alarm system impairment | > 4 hrs / 24 hr | NFPA 72 |
| Sprinkler system impairment | > 10 hrs / 24 hr | NFPA 25 |
| Hot work on site | During + 30 min after | NFPA 51B |
| Active construction / demolition | Per fire safety plan | NFPA 241 |